Kapitel 5

Wiring Examples

The following examples illustrate typical applications. Dashed connections are optional. Fuse protection, conductor protection, and the sizing of the discharge resistor must be adapted to the specific application. The discharge resistor can be dimensioned in accordance with Chapter 5.3.

5.1Redundant Discharge

Both channels are connected to the same DC-link, each using its own discharge resistor.

Redundant discharge of a DC-link
Figure 3: Redundant discharge of a DC-link

Each channel discharges a separate DC-link.

Discharge zwo separate DC-links
Figure 4: Discharge zwo separate DC-links

5.3Discharge Time and Energy Sizing

The time until the voltage Ures has decreased to

t=RC⋅ln⁡(U0Ures)t = R C \cdot \ln\left(\frac{U_0}{U_{res}}\right)

The discharge resistor must be rated for the maximum pulse power occurring during discharge

Pi=U2RP_i = \frac{U^2}{R}

If discharge occurs at intervals of T[s], the resistor must be rated for a continuous power of at least

P=C⋅U22⋅TP=\frac{C\cdot U^2}{2\cdot T}

Several example values are shown in Table 1

Table 1: Example Values for R = 100 Ω, U0 = 1500 V, Ures = 60 V, T = 120 s

Capacitance Ct [ms]Pi[kW]P[W]
100 µF3222.51
1 mF32222.510
10 mF (max.)330022.5100