Wiring Examples
The following examples illustrate typical applications. Dashed connections are optional. Fuse protection, conductor protection, and the sizing of the discharge resistor must be adapted to the specific application. The discharge resistor can be dimensioned in accordance with Chapter 5.3.
5.1Redundant Discharge
Both channels are connected to the same DC-link, each using its own discharge resistor.
5.2Two separate DC-links
Each channel discharges a separate DC-link.
5.3Discharge Time and Energy Sizing
The time until the voltage Ures has decreased to
The discharge resistor must be rated for the maximum pulse power occurring during discharge
If discharge occurs at intervals of T[s], the resistor must be rated for a continuous power of at least
Several example values are shown in Table 1
Table 1: Example Values for R = 100 Ω, U0 = 1500 V, Ures = 60 V, T = 120 s
| Capacitance C | t [ms] | Pi[kW] | P[W] |
|---|---|---|---|
| 100 µF | 32 | 22.5 | 1 |
| 1 mF | 322 | 22.5 | 10 |
| 10 mF (max.) | 3300 | 22.5 | 100 |