Kapitel 2

Connections

Simplified Block Diagram
Figure 2: Simplified Block Diagram
SignalDescription
+24 VSupply 24 V DC
GNDGround
In+1 → In−1Channel 1 control, low active, Connect 24 V and the discharge will be turned off.
In+2 → In−2Channel 2 control, low active, Connect 24 V and the discharge will be turned off.
DC1+ → DC1−DC-Voltage channel 1, max 1500 V
DC2+ → DC2−DC-Voltage channel 2, max 1500 V
R1.1 / R1.2Discharge Resistor channel 1, recomended 100 Ω
R2.1 / R2.2Discharge Resistor channel 2, recomended 100 Ω
Int1.NC1 /Int1.NC2Interlock Channel 1, normaly closed, opens when the discharge is active
Int1.NO1 /Int1.NO2Interlock Channel 1, normaly open, closes when the discharge is active
Status1Status signal channel 1: Output 24 V relative to ground if discharge inaktive. When a current of 0.6 A has flowed through the resistor, the Status switch to 0 V
Status2Status signal channel 2: Output 24 V relative to ground if discharge inaktive. When a current of 0.6 A has flowed through the resistor, the Status switch to 0 V
Int2.NC1 /Int2.NC2Interlock Channel 2, normaly closed, opens when the discharge is active
Int2.NO1 /Int2.NO2Interlock Channel 2, normaly open, closes when the discharge is active