Functional Description
4.1Operating Concept
The IRS Discharge Unit SSR replaces conventional discharge relays. When discharge is activated, the unit connects the DC-link to be discharged (DCx+, DCx−) to an externally connected discharge resistor (Rx.1, Rx.2). The energy stored in the DC-link is dissipated as heat in the discharge resistor.
The two channels are galvanically isolated from each other and from the 24 V control side. They can be used either to discharge two separate DC links independently or to provide redundant discharge of a single DC link.
For basic operation, a 24 V supply voltage and a 24 V control signal are required. The status signal and interlock contacts are optional and can be used as required by the application.
4.2Control
Control is provided via the galvanically isolated inputs In+x / In−x for each channel and is active-low:
|p0.25|p0.2|>
p0.4|
Input & Level & State
In+x / In−x & 24 V (High) & Discharge inactive
In+x / In−x & 0 V (Low) & Discharge aktiv
If the control line is interrupted or the control voltage is lost, discharge is activated automatically.
4.3Status Feedback
During discharge, the discharge current is monitored. If a current of at least 0.6 A flows, the Status x output switches from 24 V to 0 V and remains latched. The signal is reset as soon as the channel is driven with 24 V again (discharge disabled).
A 100 Ω discharge resistor with open-circuit failure mode is recommended for the IRS Discharge Unit SSR. This enables immediate detection of a resistor fault.
For proper status signal evaluation, a minimum voltage of
must be present at the high-voltage side. The status signal can optionally be read by any control system for feedback purposes. The signal is referenced to the supply voltage GND.
4.4Interlock-Contacts
Each channel provides two potential-free contacts that switch according to the discharge state. The contacts are implemented as wear-free solid-state relays and are suitable for signal voltages up to 32 V AC/DC.
|p0.27|p0.13|p0.25|p0.25| Connection & Type & Discharge inactive & Discharge active
Intx.NC1 / Intx.NC2 & normally closed & closed & open
Intx.NO1 / Intx.NO2 & normally open & open & closed
The contacts can be wired in series with door switches, light curtains, or thermal contacts and integrated into safety circuits, such as safety relays or safety PLCs. Typical applications include:
- normally closed: In the enable circuit of the precharge circuit or mains contactor, preventing the DC-link from being energized while a discharge process is active.
- normally open: Indication of an active discharge process, e.g. via an indicator lamp or a control system input.
4.5Failure Behavior
The discharge circuit is designed to fail safe. Any failure on the control side automatically initiates the discharge process.
- Control signal interruption or loss of the control voltage: The active-low control design ensures that discharge is activated automatically.
- Loss of the 24 V-supply voltage: The unit is designed to discharge by default whenever voltage is present on the high-voltage side
- Signal states without 24 V: Both interlock contacts are open (the NC contact inhibits charging), and the status signal is at 0 V.