IRS Discharge Unit SSR

Semiconductor-based discharge unit for
DC-link circuits up to 1500 V

Chapter 1

Features

  • Discharging DC-link circuits up to 1500 V
  • Discharge current up to 15 A (at 100 Ω, 1500 V)
  • Designed for DC-link capacitances up to 10 mF
  • Two independent, electrically isolated channels, usable individually or in a redundant configuration
  • Solid-state switches instead of relays: long service life, no contact wear, no sticking, no arcing
  • Fail-safe: Discharge in the event of a line break, control failure, or failure of the 24 V power supply
  • Potential-free interlock contacts per channel (normally open and normally closed)
  • Status signal per channel confirming that a discharge current has flowed
  • No cooling required
  • Standard version for 100 Ω discharge resistor; other variants available upon request
  • Compact design; mounting on TS35 top-hat rail
Top View
Figure 1: Top View
Chapter 2

Connections

Simplified Block Diagram
Figure 2: Simplified Block Diagram
SignalDescription
+24 VSupply 24 V DC
GNDGround
In+1 → In−1Channel 1 control, low active, Connect 24 V and the discharge will be turned off.
In+2 → In−2Channel 2 control, low active, Connect 24 V and the discharge will be turned off.
DC1+ → DC1−DC-Voltage channel 1, max 1500 V
DC2+ → DC2−DC-Voltage channel 2, max 1500 V
R1.1 / R1.2Discharge Resistor channel 1, recomended 100 Ω
R2.1 / R2.2Discharge Resistor channel 2, recomended 100 Ω
Int1.NC1 /Int1.NC2Interlock Channel 1, normaly closed, opens when the discharge is active
Int1.NO1 /Int1.NO2Interlock Channel 1, normaly open, closes when the discharge is active
Status1Status signal channel 1: Output 24 V relative to ground if discharge inaktive. When a current of 0.6 A has flowed through the resistor, the Status switch to 0 V
Status2Status signal channel 2: Output 24 V relative to ground if discharge inaktive. When a current of 0.6 A has flowed through the resistor, the Status switch to 0 V
Int2.NC1 /Int2.NC2Interlock Channel 2, normaly closed, opens when the discharge is active
Int2.NO1 /Int2.NO2Interlock Channel 2, normaly open, closes when the discharge is active
Chapter 3

Technical Data

3.1Power Supply and Control

ParameterValue
Supply24 V DC
Power consumption1 W
Controll In±x24 V
Input current In±xca. 6 mA bei 24 V
Status24 V related to GND
Turn on delay → Discharge580 ms

3.2Discharge Circuit (per Channel)

ParameterValue
Discharge voltagemax. 1500 V DC
Max. DC-link capacitance10 mF (bei 100 Ω)
Discharge Resistor (external)Standard 100 Ω, weitere Varianten auf Anfrage
Status signal threshold0,6 A (entspricht 60 V bei 100 Ω)
Quiescent current from the DC-link (Discharge OFF)<1 mA bei 1500 V

3.3Interlock Contacts (per Channel)

ParameterValue
Configuration1 Normally closed (NC) and 1 normally open (NO), potential-free, solid-state relay
Max. switching voltage32 V AC/DC

3.4Insulation and Environmental Conditions

Parameter
Insulation voltage, control side / high-voltage side
Insulation voltage, channel 1 / channel 2
Overvoltage categoryII
Pollution degree2
Degree of protectionIP20
Operating temperature
Storage temperature
Relative humidity

3.5Mechanical Specifications

ParameterValue
Dimensions (B × H × T)90 × 63 × 72 mm
Weight140 g
MountingHutschiene TS35 (EN 60715)
Connection (high-voltage side)Snap-in-Connector, pitch 7,5 mm (Weidmüller TERM BLOCK PLUG 2 POS 7.50), 0.5-4 mm²
Connection (control side)Push-in-Connector, pitch 3,5 mm (Weidmüller BL/SL 3.50), 0.14-1.5 mm²

3.6Standards and Approvals

ParameterValue
ComplianceRoHS

¹ The peak current depends on the discharge resistor and is calculated as Imax = UDC / R. For a 100 Ω discharge resistor at 1500 V DC, the peak current is 15 A.

Chapter 4

Functional Description

4.1Operating Concept

The IRS Discharge Unit SSR replaces conventional discharge relays. When discharge is activated, the unit connects the DC-link to be discharged (DCx+, DCx−) to an externally connected discharge resistor (Rx.1, Rx.2). The energy stored in the DC-link is dissipated as heat in the discharge resistor.

The two channels are galvanically isolated from each other and from the 24 V control side. They can be used either to discharge two separate DC links independently or to provide redundant discharge of a single DC link.

For basic operation, a 24 V supply voltage and a 24 V control signal are required. The status signal and interlock contacts are optional and can be used as required by the application.

4.2Control

Control is provided via the galvanically isolated inputs In+x / In−x for each channel and is active-low:

|p0.25|p0.2|>

p0.4|

Input & Level & State
In+x / In−x & 24 V (High) & Discharge inactive
In+x / In−x & 0 V (Low) & Discharge aktiv

If the control line is interrupted or the control voltage is lost, discharge is activated automatically.

4.3Status Feedback

During discharge, the discharge current is monitored. If a current of at least 0.6 A flows, the Status x output switches from 24 V to 0 V and remains latched. The signal is reset as soon as the channel is driven with 24 V again (discharge disabled).
A 100 Ω discharge resistor with open-circuit failure mode is recommended for the IRS Discharge Unit SSR. This enables immediate detection of a resistor fault.

For proper status signal evaluation, a minimum voltage of

U=I⋅R=0,6 A⋅100 Ω=60 V.U = I \cdot R = 0,6\,A \cdot 100\,\Omega = 60\,V.

must be present at the high-voltage side. The status signal can optionally be read by any control system for feedback purposes. The signal is referenced to the supply voltage GND.

4.4Interlock-Contacts

Each channel provides two potential-free contacts that switch according to the discharge state. The contacts are implemented as wear-free solid-state relays and are suitable for signal voltages up to 32 V AC/DC.

|p0.27|p0.13|p0.25|p0.25| Connection & Type & Discharge inactive & Discharge active
Intx.NC1 / Intx.NC2 & normally closed & closed & open
Intx.NO1 / Intx.NO2 & normally open & open & closed

The contacts can be wired in series with door switches, light curtains, or thermal contacts and integrated into safety circuits, such as safety relays or safety PLCs. Typical applications include:

  • normally closed: In the enable circuit of the precharge circuit or mains contactor, preventing the DC-link from being energized while a discharge process is active.
  • normally open: Indication of an active discharge process, e.g. via an indicator lamp or a control system input.

4.5Failure Behavior

The discharge circuit is designed to fail safe. Any failure on the control side automatically initiates the discharge process.

  • Control signal interruption or loss of the control voltage: The active-low control design ensures that discharge is activated automatically.
  • Loss of the 24 V-supply voltage: The unit is designed to discharge by default whenever voltage is present on the high-voltage side
  • Signal states without 24 V: Both interlock contacts are open (the NC contact inhibits charging), and the status signal is at 0 V.
Chapter 5

Wiring Examples

The following examples illustrate typical applications. Dashed connections are optional. Fuse protection, conductor protection, and the sizing of the discharge resistor must be adapted to the specific application. The discharge resistor can be dimensioned in accordance with Chapter 5.3.

5.1Redundant Discharge

Both channels are connected to the same DC-link, each using its own discharge resistor.

Redundant discharge of a DC-link
Figure 3: Redundant discharge of a DC-link

Each channel discharges a separate DC-link.

Discharge zwo separate DC-links
Figure 4: Discharge zwo separate DC-links

5.3Discharge Time and Energy Sizing

The time until the voltage Ures has decreased to

t=RC⋅ln⁡(U0Ures)t = R C \cdot \ln\left(\frac{U_0}{U_{res}}\right)

The discharge resistor must be rated for the maximum pulse power occurring during discharge

Pi=U2RP_i = \frac{U^2}{R}

If discharge occurs at intervals of T[s], the resistor must be rated for a continuous power of at least

P=C⋅U22⋅TP=\frac{C\cdot U^2}{2\cdot T}

Several example values are shown in Table 1

Table 1: Example Values for R = 100 Ω, U0 = 1500 V, Ures = 60 V, T = 120 s

Capacitance Ct [ms]Pi[kW]P[W]
100 µF3222.51
1 mF32222.510
10 mF (max.)330022.5100
Chapter 6

Mounting

  • Mounting on a TS35 DIN rail inside a control cabinet; mounting orientation is unrestricted.
  • Install the discharge resistors so that the generated heat cannot affect the unit or other components.
Chapter 7

Ordering Options

The IRS Discharge Unit SSR is available as a standalone unit or as a complete kit with matching discharge resistors and the IRS Vol-Tran residual voltage monitoring device.

VariantPart-Nr.Discription
Discharge Unit SSR131030IRS Discharge Unit SSR
Kit with discharge resistores131066IRS Discharge Unit SSR × Discharge Resistores 100 Ω / 300 W with integrated Thermal Switches

7.1Individual Parts

Part-Nr.Discription
131030IRS Discharge Unit SSR
128930Discharge Resistor 100 Ω / 300 W (REOHM BW 151/300/100)

Other resistance values available on request.