Semiconductor-based discharge unit for
DC-link circuits up to 1500 V
Features
- Discharging DC-link circuits up to 1500 V
- Discharge current up to 15 A (at 100 Ω, 1500 V)
- Designed for DC-link capacitances up to 10 mF
- Two independent, electrically isolated channels, usable individually or in a redundant configuration
- Solid-state switches instead of relays: long service life, no contact wear, no sticking, no arcing
- Fail-safe: Discharge in the event of a line break, control failure, or failure of the 24 V power supply
- Potential-free interlock contacts per channel (normally open and normally closed)
- Status signal per channel confirming that a discharge current has flowed
- No cooling required
- Standard version for 100 Ω discharge resistor; other variants available upon request
- Compact design; mounting on TS35 top-hat rail
Connections
| Signal | Description |
|---|---|
| +24 V | Supply 24 V DC |
| GND | Ground |
| In+1 → In−1 | Channel 1 control, low active, Connect 24 V and the discharge will be turned off. |
| In+2 → In−2 | Channel 2 control, low active, Connect 24 V and the discharge will be turned off. |
| DC1+ → DC1− | DC-Voltage channel 1, max 1500 V |
| DC2+ → DC2− | DC-Voltage channel 2, max 1500 V |
| R1.1 / R1.2 | Discharge Resistor channel 1, recomended 100 Ω |
| R2.1 / R2.2 | Discharge Resistor channel 2, recomended 100 Ω |
| Int1.NC1 /Int1.NC2 | Interlock Channel 1, normaly closed, opens when the discharge is active |
| Int1.NO1 /Int1.NO2 | Interlock Channel 1, normaly open, closes when the discharge is active |
| Status1 | Status signal channel 1: Output 24 V relative to ground if discharge inaktive. When a current of 0.6 A has flowed through the resistor, the Status switch to 0 V |
| Status2 | Status signal channel 2: Output 24 V relative to ground if discharge inaktive. When a current of 0.6 A has flowed through the resistor, the Status switch to 0 V |
| Int2.NC1 /Int2.NC2 | Interlock Channel 2, normaly closed, opens when the discharge is active |
| Int2.NO1 /Int2.NO2 | Interlock Channel 2, normaly open, closes when the discharge is active |
Technical Data
3.1Power Supply and Control
| Parameter | Value |
|---|---|
| Supply | 24 V DC |
| Power consumption | 1 W |
| Controll In±x | 24 V |
| Input current In±x | ca. 6 mA bei 24 V |
| Status | 24 V related to GND |
| Turn on delay → Discharge | 580 ms |
3.2Discharge Circuit (per Channel)
| Parameter | Value |
|---|---|
| Discharge voltage | max. 1500 V DC |
| Max. DC-link capacitance | 10 mF (bei 100 Ω) |
| Discharge Resistor (external) | Standard 100 Ω, weitere Varianten auf Anfrage |
| Status signal threshold | 0,6 A (entspricht 60 V bei 100 Ω) |
| Quiescent current from the DC-link (Discharge OFF) | <1 mA bei 1500 V |
3.3Interlock Contacts (per Channel)
| Parameter | Value |
|---|---|
| Configuration | 1 Normally closed (NC) and 1 normally open (NO), potential-free, solid-state relay |
| Max. switching voltage | 32 V AC/DC |
3.4Insulation and Environmental Conditions
| Parameter | |
|---|---|
| Insulation voltage, control side / high-voltage side | |
| Insulation voltage, channel 1 / channel 2 | |
| Overvoltage category | II |
| Pollution degree | 2 |
| Degree of protection | IP20 |
| Operating temperature | |
| Storage temperature | |
| Relative humidity |
3.5Mechanical Specifications
| Parameter | Value |
|---|---|
| Dimensions (B × H × T) | 90 × 63 × 72 mm |
| Weight | 140 g |
| Mounting | Hutschiene TS35 (EN 60715) |
| Connection (high-voltage side) | Snap-in-Connector, pitch 7,5 mm (Weidmüller TERM BLOCK PLUG 2 POS 7.50), 0.5-4 mm² |
| Connection (control side) | Push-in-Connector, pitch 3,5 mm (Weidmüller BL/SL 3.50), 0.14-1.5 mm² |
3.6Standards and Approvals
| Parameter | Value |
|---|---|
| Compliance | RoHS |
¹ The peak current depends on the discharge resistor and is calculated as Imax = UDC / R. For a 100 Ω discharge resistor at 1500 V DC, the peak current is 15 A.
Functional Description
4.1Operating Concept
The IRS Discharge Unit SSR replaces conventional discharge relays. When discharge is activated, the unit connects the DC-link to be discharged (DCx+, DCx−) to an externally connected discharge resistor (Rx.1, Rx.2). The energy stored in the DC-link is dissipated as heat in the discharge resistor.
The two channels are galvanically isolated from each other and from the 24 V control side. They can be used either to discharge two separate DC links independently or to provide redundant discharge of a single DC link.
For basic operation, a 24 V supply voltage and a 24 V control signal are required. The status signal and interlock contacts are optional and can be used as required by the application.
4.2Control
Control is provided via the galvanically isolated inputs In+x / In−x for each channel and is active-low:
|p0.25|p0.2|>
p0.4|
Input & Level & State
In+x / In−x & 24 V (High) & Discharge inactive
In+x / In−x & 0 V (Low) & Discharge aktiv
If the control line is interrupted or the control voltage is lost, discharge is activated automatically.
4.3Status Feedback
During discharge, the discharge current is monitored. If a current of at least 0.6 A flows, the Status x output switches from 24 V to 0 V and remains latched. The signal is reset as soon as the channel is driven with 24 V again (discharge disabled).
A 100 Ω discharge resistor with open-circuit failure mode is recommended for the IRS Discharge Unit SSR. This enables immediate detection of a resistor fault.
For proper status signal evaluation, a minimum voltage of
must be present at the high-voltage side. The status signal can optionally be read by any control system for feedback purposes. The signal is referenced to the supply voltage GND.
4.4Interlock-Contacts
Each channel provides two potential-free contacts that switch according to the discharge state. The contacts are implemented as wear-free solid-state relays and are suitable for signal voltages up to 32 V AC/DC.
|p0.27|p0.13|p0.25|p0.25| Connection & Type & Discharge inactive & Discharge active
Intx.NC1 / Intx.NC2 & normally closed & closed & open
Intx.NO1 / Intx.NO2 & normally open & open & closed
The contacts can be wired in series with door switches, light curtains, or thermal contacts and integrated into safety circuits, such as safety relays or safety PLCs. Typical applications include:
- normally closed: In the enable circuit of the precharge circuit or mains contactor, preventing the DC-link from being energized while a discharge process is active.
- normally open: Indication of an active discharge process, e.g. via an indicator lamp or a control system input.
4.5Failure Behavior
The discharge circuit is designed to fail safe. Any failure on the control side automatically initiates the discharge process.
- Control signal interruption or loss of the control voltage: The active-low control design ensures that discharge is activated automatically.
- Loss of the 24 V-supply voltage: The unit is designed to discharge by default whenever voltage is present on the high-voltage side
- Signal states without 24 V: Both interlock contacts are open (the NC contact inhibits charging), and the status signal is at 0 V.
Wiring Examples
The following examples illustrate typical applications. Dashed connections are optional. Fuse protection, conductor protection, and the sizing of the discharge resistor must be adapted to the specific application. The discharge resistor can be dimensioned in accordance with Chapter 5.3.
5.1Redundant Discharge
Both channels are connected to the same DC-link, each using its own discharge resistor.
5.2Two separate DC-links
Each channel discharges a separate DC-link.
5.3Discharge Time and Energy Sizing
The time until the voltage Ures has decreased to
The discharge resistor must be rated for the maximum pulse power occurring during discharge
If discharge occurs at intervals of T[s], the resistor must be rated for a continuous power of at least
Several example values are shown in Table 1
Table 1: Example Values for R = 100 Ω, U0 = 1500 V, Ures = 60 V, T = 120 s
| Capacitance C | t [ms] | Pi[kW] | P[W] |
|---|---|---|---|
| 100 µF | 32 | 22.5 | 1 |
| 1 mF | 322 | 22.5 | 10 |
| 10 mF (max.) | 3300 | 22.5 | 100 |
Mounting
- Mounting on a TS35 DIN rail inside a control cabinet; mounting orientation is unrestricted.
- Install the discharge resistors so that the generated heat cannot affect the unit or other components.
Ordering Options
The IRS Discharge Unit SSR is available as a standalone unit or as a complete kit with matching discharge resistors and the IRS Vol-Tran residual voltage monitoring device.
| Variant | Part-Nr. | Discription |
|---|---|---|
| Discharge Unit SSR | 131030 | IRS Discharge Unit SSR |
| Kit with discharge resistores | 131066 | IRS Discharge Unit SSR × Discharge Resistores 100 Ω / 300 W with integrated Thermal Switches |
7.1Individual Parts
| Part-Nr. | Discription |
|---|---|
| 131030 | IRS Discharge Unit SSR |
| 128930 | Discharge Resistor 100 Ω / 300 W (REOHM BW 151/300/100) |
Other resistance values available on request.