## Touchpad screens

### Home

![Home screen with the areas Aggregat (unit), Kühlkreislauf 1 and Kühlkreislauf 2 (cooling circuit 1 and 2)](/docs/assets/irs-icecube-pro/images/ice-screen-home.png)

The following functions are available in the **Aggregat** (unit) area on the left:

- **Freigabe** (enable) is granted with the gray button; as soon as it has been granted, the green indicator lights up
- **Reset** must be pressed when the blue indicator next to it flashes, to acknowledge errors
- with **Auto Fill**, after both cooling circuits have been blown out, the system checks whether the fill level is still at maximum. If not, a valve opens the circuit for refilling, so that the fill level is automatically kept at the correct level

The following status indicators are also available:

- **Befüllen aktiv** (filling active)
- **Alles OK** (all OK)
- pH value measurement (IRS ICEcube PRO+ only)
- Conductivity measurement (IRS ICEcube PRO+ only)

The target temperature specifies the desired cooling water temperature with which the DUT is to be temperature-controlled. The water temperature of the facility water connection must be entered.

The following functions are available in the **Kühlkreis 1** and **Kühlkreis 2** (cooling circuit 1 and 2) areas:

- activating the pump with the **Pumpe** (pump) button
- blowing out the cooling water with the **Ausblasen** (blow out) button
- leak test of the DUT circuit with the **Dichteprüfung** (leak test) button

The following status indicators are also available:

- **Ist-Temperatur** (actual temperature): measured temperature of the supply line
- **Ist-Durchfluss** (actual flow): measured flow
- **Druck** (pressure): measured pressure
- **Kreislauf befüllt** (circuit filled) indicator

### Configuration

![Konfiguration screen with the areas Konfiguration, Kühlkreislauf 1 and Kühlkreislauf 2 (configuration, cooling circuit 1 and 2)](/docs/assets/irs-icecube-pro/images/ice-screen-konfiguration.png)

The following functions are available in the **Konfiguration** (configuration) area on the left:

- select the **Kreise gekoppelt** (circuits coupled) button if the circuits are connected to each other

> **Note**
> The **Kreise gekoppelt** button must be activated as soon as both circuits are connected to each other to generate more flow

- Use the **Pumpe regelt auf** (pump controls to) rotary switch to switch between pressure-controlled and flow-controlled operation

The following status indicators are also available:

The target temperature of the DUT is entered manually here (10–70 °C).

The following functions are available in the **Kühlkreislauf 1** and **Kühlkreislauf 2** (cooling circuit 1 and 2) areas:

- Setting the target pressure in **Soll-Druck** (0–9 bar)
- Setting the target flow in **Soll-Durchfluss** (0–50 l/min)
- Setting the temperature correction factor in **T Korrekturfaktor**
- Setting the temperature correction value in **T Korrekturwert** (offset of the temperature sensor)
- Setting the continuous blow-out duration in **Ausblasdauer kontinuierlich**
- Setting the pulsed blow-out duration in **Ausblasdauer Pulsen**

The following status indicators are also available:

- **Ist-Temperatur**
- **Ist-Durchfluss**
- Pressure
- **Kreislauf befüllt** light

### Status and error log

![Status & Error Log screen with error and status lights, software version and heating element temperatures](/docs/assets/irs-icecube-pro/images/ice-screen-status-error-log.png)

The various error indicators are listed here; an error is present when they light up red. Troubleshooting is described in [Troubleshooting](/en/docs/irs-icecube-pro/logo#troubleshooting).

The gray **Dichteprüfung KK** (leak test, cooling circuit) button performs a pressure test of the cooling water circuits. The circuit is pressurized with compressed air and the pressure drop is measured, which allows conclusions to be drawn about correct and leak-tight lines / DUTs. The green and yellow lights below it show the status.

The software version and the status, including the heating element temperatures, are shown in the lower part.

### Switching counter

![Schaltzähler (switching counter) screen for the solenoid valves Q1 to Q11](/docs/assets/irs-icecube-pro/images/ice-screen-schaltzaehler.png)

The switching cycles of the solenoid valves Q1–Q11 are recorded and displayed here for maintenance and repair measures.

## Troubleshooting

**Not-Aus Extern** (external emergency stop):

Make sure that the system can be switched on again safely, unlock the emergency stop, and on the screen first reset the cooling unit and then enable it again.

**Füllstand &lt; Min** (fill level below minimum):

Fill up the cooling water to maximum via the connection provided for this purpose on the cooling unit.

**Fill level above maximum:**

Drain the cooling water via one of the two cooling circuits. Connect a hose to the supply of KK1 or KK2 (cooling circuit 1 or 2) and place the hose in a collecting container. Switch on the respective pump to pump the coolant out of the tank.

> **Note**
> When draining completely, do not let the pump run dry

**Overpressure cooling circuit 1 and 2:**

Stop the pumps. Check the hoses for kinks. Make sure that no object is standing on the hoses or interrupting or impairing the flow. With pressure-controlled pump control, reduce the target pressure.

**Overtemperature heating element 1 and 2:**

Deactivate the heating elements. Reduce the target temperature in the tank.

**Frequency converter 1 and 2:**

Switch off the IRS ICEcube.

## LOGO! Modbus TCP mapping

| I/O (E/A) | Block type (LOGO) | Description | Address | IEC type | Category | Offset S7 | Info |
| --- | --- | --- | --- | --- | --- | --- | --- |
| E VB-0-0 | NI | Reset Safety | 1 | coil | write | 0 | Edge |
| E VB-0-2 | NI | Blow-out KK1 | 3 | coil | write | 0 | Edge |
| E VB-0-3 | NI | Blow-out KK2 | 4 | coil | write | 0 | Edge |
| E VB-0-4 | NI | Blow-out reserve KK1 | 5 | coil | write | 0 | Edge |
| E VB-0-5 | NI | Blow-out reserve KK1 | 6 | coil | write | 0 | Edge |
| E VB-0-6 | NI | Activate auto fill | 7 | coil | write | 0 | Edge |
| E VB-0-7 | NI | Enable | 8 | coil | write | 0 | Edge |
| E VB-1-0 | NI | Pump request KK1 | 9 | coil | write | 0 | Edge |
| E VB-1-1 | NI | Pump request KK2 | 10 | coil | write | 0 | Edge |
| E VB-1-2 | NI | Leak test KK1 | 11 | coil | write | 0 | Edge |
| E VB-1-3 | NI | Leak test KK2 | 12 | coil | write | 0 | Edge |
| A VB-10-0 | NQ | Flashes on safety error | 81 | coil | read | 0 | Feedback |
| A VB-10-1 | NQ | Enable active | 82 | coil | read | 0 | Feedback |
| A VB-10-2 | NQ | Filling process active | 83 | coil | read | 0 | Feedback |
| A VB-10-3 | NQ | Blow-out KK1 active | 84 | coil | read | 0 | Feedback |
| A VB-10-4 | NQ | Blow-out KK2 active | 85 | coil | read | 0 | Feedback |
| A VB-10-5 | NQ | Pump KK1 active | 86 | coil | read | 0 | Feedback |
| A VB-10-6 | NQ | Pump KK2 active | 87 | coil | read | 0 | Feedback |
| A VB-10-7 | NQ | External emergency stop | 88 | coil | read | 0 | Feedback |
| A VB-11-0 | NQ | Fill level min | 89 | coil | read | 0 | Feedback |
| A VB-11-1 | NQ | Fill level max | 90 | coil | read | 0 | Feedback |
| A VB-11-2 | NQ | KK1 filled | 91 | coil | read | 0 | Feedback |
| A VB-11-3 | NQ | KK2 filled | 92 | coil | read | 0 | Feedback |
| M1 | M | Pump KK1 | 8257 | coil | read | 0 | Status pump requested |
| M2 | M | Pump KK2 | 8258 | coil | read | 0 | Status pump requested |
| M3 | M | Blow-out KK1 active | 8259 | coil | read | 0 | Status |
| M4 | M | Blow-out KK2 active | 8260 | coil | read | 0 | Status |
| M5 | M | Reverse blow-out KK1 active | 8261 | coil | read | 0 | Status |
| M6 | M | Reverse blow-out KK2 active | 8262 | coil | read | 0 | Status |
| M7 | M | Safety All OK | 8263 | coil | read | 0 | Status |
| M9 | M | KK1 filled | 8265 | coil | read | 0 | Status |
| M10 | M | KK2 filled | 8266 | coil | read | 0 | Status |
| M11 | M | External emergency stop | 8267 | coil | read | 0 | Status |
| M12 | M | Enable | 8268 | coil | read | 0 | Status |
| M13 | M | Auto fill active | 8269 | coil | read | 0 | Status |
| M15 | M | Fill level min. | 8271 | coil | read | 0 | Status |
| M16 | M | Fill level max. | 8272 | coil | read | 0 | Status |
| M18 | M | fb heating element 1 | 8274 | coil | read | 0 | Feedback |
| M19 | M | fb heating element 2 | 8275 | coil | read | 0 | Feedback |
| M20 | M | Leak test KK1 running | 8276 | coil | read | 0 | Status |
| M21 | M | Leak test KK2 running | 8277 | coil | read | 0 | Status |
| M22 | M | Leak test KK1 OK | 8278 | coil | read | 0 | Feedback |
| M23 | M | Leak test KK2 OK | 8279 | coil | read | 0 | Feedback |
| M32 | M | Flow control high, pressure control low | 8288 | coil | write | 0 | ON/OFF (high/low) |
| M33 | M | Error circuits coupled | 8289 | coil | write | 0 | Error |
| M37 | M | Error overtemperature heating element 1 | 8293 | coil | read | 0 | Error |
| M38 | M | Error overtemperature heating element 2 | 8294 | coil | read | 0 | Error |
| M39 | M | Error FU1 (frequency converter 1) | 8295 | coil | read | 0 | Error |
| M40 | M | Error FU 2 (frequency converter 2) | 8296 | coil | read | 0 | Error |
| M41 | M | Error overpressure KK1 | 8297 | coil | read | 0 | Error |
| M42 | M | Error overpressure KK2 | 8298 | coil | read | 0 | Error |
| AM1 | AM | Actual temp KK1 supply | 529 | holding register | read | 40000 | Read Int |
| AM2 | AM | Actual temp KK2 supply | 530 | holding register | read | 40000 | Read Int |
| AM3 | AM | Actual flow KK1 | 531 | holding register | read | 40000 | Read Int |
| AM4 | AM | Actual flow KK2 | 532 | holding register | read | 40000 | Read Int |
| AM5 | AM | Actual pressure KK1 | 533 | holding register | read | 40000 | Read Int |
| AM6 | AM | Actual pressure KK2 | 534 | holding register | read | 40000 | Read Int |
| AM7 | AM | pH value | 535 | holding register | read | 40000 | Read Int |
| AM8 | AM | Conductivity | 536 | holding register | read | 40000 | Read Int |
| AM9 | AM | Temp heating element 1 | 537 | holding register | read | 40000 | Read Int |
| AM10 | AM | Temp heating element 2 | 538 | holding register | read | 40000 | Read Int |
| AM11 | AM | Heating element interlock; AM11=0 control active; AM11=1 heating element 1 deactivated; AM11=2 heating element 2 deactivated; AM11=3 both heating elements are deactivated | 539 | holding register | read | 40000 | Read Int |
| AM14 | AM | Software version LOGO | 542 | holding register | read | 40000 | Status |
| AM27 | AM | Blow-out duration in s (default 5 s, manual &lt;1) | 555 | holding register | read/write | 40000 | Set/Read Int |
| AM28 | AM | Pulse duration in s (default 5 s, manual &lt;1) | 556 | holding register | read/write | 40000 | Set/Read Int |
| AM29 | AM | Overpressure threshold (default 2.7 bar) | 557 | holding register | read/write | 40000 | Set/Read Int |
| AM30 | AM | Correction factor temp KK1 | 568 | holding register | write | 40000 | Set Int |
| AM31 | AM | Correction factor temp KK1 | 569 | holding register | write | 40000 | Set Int |
| AM32 | AM | Correction factor temp KK2 | 570 | holding register | write | 40000 | Set Int |
| AM33 | AM | Correction factor temp KK2 | 571 | holding register | write | 40000 | Set Int |
| AM34 | AM | Target temp | 572 | holding register | write | 40000 | Set Int |
| AM35 | AM | Target flow KK1 | 573 | holding register | write | 40000 | Set Int |
| AM36 | AM | Target flow KK2 | 574 | holding register | write | 40000 | Set Int |
| AM37 | AM | Target pressure KK1 | 575 | holding register | write | 40000 | Set Int |
| AM38 | AM | Target pressure KK2 | 576 | holding register | write | 40000 | Set Int |
| AM42 | AM | Facility water temperature | 580 | holding register | write | 40000 | Set Int |
| I3 | I | Auxiliary contact heating element 1 | 3 | Dig. input | read | 10000 | Feedback |
| I4 | I | Auxiliary contact heating element 2 | 4 | Dig. input | read | 10000 | Feedback |